Description
Item Description:
The VESDA VLC detector has been specifically designed to provide all the benefits of aspirating smoke detection, including very early warning, in single environment small areas and where space is a premium. The VLC combines the well-proven VESDA VLP detection technology with a modified aspirator design, and incorporates them into a compact enclosure with a simplified display. The VLC is available in two versions, one that interfaces via relays only (RO) and one that interfaces via relays and VESDAnet (VN). The VN version is compatible with the remote Display Module, which allows the current status of the detector to be reported in the most convenient location. The remote Display Module has 7 remote relays to support any combination of signaling that may be demanded by the application. The VN version allows several detectors to be linked together on VESDAnet thereby allowing one to act as a reference detector for other VESDA detectors.
Product Specs:
Brand | Xtralis |
MPN | VLC-500 |
Model | VLC |
Supply Voltage | 18-30 VDC |
Power Consumption | 5.4 W quiescent, 5.9 W with alarm |
Current consumption | 225 mA quiescent, 245 mA with alarm |
Dimensions (WHD) | 225 mm x 225 mm x 85 mm (8 7 /8” x 8 7 /8”x 3 3 /8”) |
Weight | 1.9 kg (4.2 lbs.) |
Operating conditions | Ambient: 0°C to 39°C (32°F to 103°F) * Tested: -10°C to 55°C (14°F to 131°F) Sampled Air: -20°C to 60°C (-4°F to 140°F) Humidity: 10% to 95% RH, non-condensing * Product UL listed for use from 0°C to 38°C (32°F to 104°F) |
Storage conditions (non-operational) | Humidity: Dry (<95%) Temperature: 0° to 85° C (32°F to 185°F) Must not be exposed to sunlight or other radiation sources |
Sampling network | Maximum area of coverage • Code compliant: 800 m² (8000 sq.ft) • Maximum (120sec transport time): 2,370 m² (25,500 sq.ft). Local code requirements shall take precedence |
Maximum pipe lengths | 1 x 80 m (260ft), 2 x 50 m (164ft) |
Computer design tool | ASPIRE2™ |
Pipe | Internal Diameter 15 mm–21 mm (9/16”–7/8”) External Diameter 25 mm (1”) |
Relays | 3 Relays rated 2 A @ 30 VDC Fire (NO) Pre-Alarm (NO) Alert/Fault (Maintenance & Isolate) (NC/NO) Configurable as latching or non-latching |
Cable access | 4 x 25 mm (1”) cable entries |
Cable termination | Screw Terminal blocks 0.2–2.5 sq mm (30–12 AWG) |
Alarm sensitivity range | 0.005% to 20% obs/m (0.0015% to 6.25% obs/ft) |
Threshold setting range | Alert: 0.005%–1.990% obs/m (0.0015%–0.6218% obs/ft) Pre-Alarm: 0.010%–1.995% obs/m (0.0031%–0.6234% obs/ft) Fire: 0.015%–20.00% obs/m (0.0046%–6.25% obs/ft)* *Limited to 4% obs/ft for UL |
Software features | Event log: Up to 12,000 events stored in FIFO format Smoke level, user actions, alarms and faults with time and date stamp AutoLearn: Minimum 15 minutes, maximum 15 days. Recommended minimum 14 days. During AutoLearn thresholds are NOT changed from pre-set values |
Configurable general input (24 VDC) | Standby, Mains OK or Reset/Isolate |