Description
Item Description:
NOTIFIER’s XP6-R six-relay control module provides an intelligent fire alarm system with six Form-C relays. The first module is addressed from 01 to 154 while the remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules. A single isolated set of dry relay contacts is provided for each module address, which is capable of being wired for either a normally-open or normally-closed operation. The module allows the control panel to switch these contacts on command. No supervision is provided for the controlled circuit. Each XP6-R module has panel-controlled green LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
Product Specs:
Brand | Honeywell Notifier |
MPN | XP6-R |
Model | XP6-R(A) |
Standby current | 1.45 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases) |
Alarm current | 32 mA (assumes all six relays have been switched once and all six LEDs solid ON) |
Temperature range | 32°F to 120°F (0°C to 49°C) |
Humidity | 10% to 93% non-condensing |
Dimensions | 6.8″ (17.27 cm) high x 5.8″ (14.73 cm) wide x 1.0″ (2.54 cm) deep |
Shipping weight | 1.1 lb. (0.5 kg) including packaging |
Mounting options | CHS-6 chassis, BB-25 cabinet, BB-XP cabinet, CAB-3 Series (see DN-3549) cabinet, CAB-4 Series (see DN-6857) cabinet, or EQ Series (see DN-60229) cabinet |
Wire gauge | 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²) |
Maximum SLC wiring resistance | 40 or 50 ohms, panel dependent |
Relay current | 30 mA/relay pulse (15.6 ms pulse duration), pulse under panel control |
Relay contact ratings | 30 VDC; 70.7 VAC |